Installation
Factory Support
For customized products, we recommend that you have a Peerless Pump service engineer supervise installation and startup.
This is to ensure that the machinery is properly installed. You will then also have the opportunity to review, and see implemented, factory-recommended instructions.
Location
Locate pump discharge piping and suction piping as well as auxiliary equipment, control and starting panels so that adequate access is provided for maintenance.
Adequate floor space and working room should also be provided for maintenance.
To minimize frictional head loss, locate the pump so that it can be installed with a short and direct discharge pipe and with the least number of elbows and fittings. If practical, it should be placed so that it will be accessible for inspection during operation. Pumps, drivers and controls should be protected against flooding, freezing, etc.
The suction supply system must provide the pump with Net Positive Suction Head (NPSH) equal to or greater than that required by the pump at any capacity on its operating curve. Ask your Peerless Pump representative for assistance if; you do not understand how to calculate or measure suction supply system NPSH.
Foundation
The pump must be installed on a foundation rigid enough to support the entire weight of the pump plus the weight of the fluid contained in it. Weak foundations or foundations on unstable ground can cause misalignment, vibration, and even total foundation failure.
The mass of the foundation should be sufficient, preferably five times that of the rotating element of the pumping equipment, to form a permanent and rigid support for the base plate.
Foundation and base plate bolt sizing is critical, particularly on high-pressure pumps, to adequately restrain reaction forces such as from directional flow change, system transients and sudden valve closure. Concrete foundations may have anchor bolts installed in sleeves that are two times the diameter of the bolt to allow alignment and should be located by a drawing or template.
Whether the base plate is installed prior to the pump installation or at the same time, the pump must be attached to the base plate. Check that the pump feet are clean and free of burrs and nicks.
Failure to have each component's surface machined will result in excessive vibration.
Seismic Analysis
When pumps are located in seismically active areas and for certain critical installations the pumps, supports and accessories should be earthquake-resistant. The design specifications to achieve earthquake resistance vary, depending upon geographical area, class of the equipment (defining how critical the survival of the equipment is) and the characteristics (acceleration response) of the structure or foundation supporting the pump.
Complete specifications for earthquake-resistance requirements should be supplied by the customer. This includes the following:
- The seismic criteria, such as acceleration, magnitudes, frequency spectrum, location and direction relative to pump
- The qualification procedure required, i.e., analysis, testing or a combination of these, and requirements for operability during and/or after test.
Rigging & Lifting
For typical installations, suitable overhead lifting equipment of adequate capacity to lift the driver, the entire pump (without driver) or the heaviest subassembly of the pump should be available at the job site when installing or removing the pump. Adequate headroom should be provided to accommodate the pump to be handled, including rigging.
Leveling
- Remove the supporting timbers, rope and any other equipment from the top of the foundation.
- Disconnect the coupling halves between the pump and driver.
- Lower the pump unit until the base plate is just above the foundation bolts.
- Orient the pump so that the discharge outlet and suction inlet is in the desired direction and the holes in the base align with the foundation bolts.
- Continue to lower the pump until the bolts just enter the holes in the base.
- If the foundation is concrete, place the wedges under the base plate, adjacent to the bolt holes, one under each of the four sides.
- For structural foundations (made up of I-beams or H-beams), use shims under the corners.
- Continue to slowly lower the pump until the base of the base plate rests on the wedges or anchor bolts with washers and nuts.
- By using the wedges or washers and nuts on the anchor bolts, adjust the pump suction flange center line to the correct elevation.
- While maintaining the correct elevation, adjust the nuts and washers or shims to achieve the specified levelness of 0.005" per ft. [0.4 mm per m] in both directions. The levelness should be measured by placing a precision level on the machined face of the discharge flange.
- Place a machinist's level on the discharge flange, orienting it parallel with one of the edges of the base.
- Move the wedges or add more shims until the level reading reaches 0.005" per ft. [0.4 mm per m].
- Reorient the level on the same surface, 90 ° from the original position.
- Again adjust the wedges or shims until a 0.005" [0.12 mm] level reading is reached, taking care not to upset the levelness is the first direction.
- After each adjustment, check for levelness in both directions.
- Push in or add to any loose shims to distribute the weight evenly.
- Fit nuts on the foundation bolts and tighten them gradually and uniformly.
- Check the level readings in both directions.
- If necessary, loosen the foundation bolts and readjust the wedges or shims, tighten the bolts again and check the level readings.
Grouting
After the base plate is at the correct location and leveled with a precision level, the base plate needs to be grouted to the foundation.
Grout compensates for unevenness in the foundation and base plate and minimizes vibrations levels during operations. It prevents the unit from shifting after mounting and alignment.
Only non-shrinking grouting material should be used for grouting the base plate to the foundation. Foundation bolts should not be fully tightened until the grout is hardened, usually about 48 hours after pouring.
1. Prepare the foundation surface according to the grout manufacturer's recommendations.
2. Locate the foundation bolts by the use of a template frame and provide anchorage. See the outline drawings furnished with each pump for the exact location of the foundation bolts.
3. Build a dam on the foundation, enclosing an area around the base plate that includes all alignment wedges. Allow for a grout thickness of 0.75 to 1.50" thickness [19.05 mm to 38.1 mm].
4. Pour the grout through the holes provided in the base plate or through open ends of steel channel base plates. While pouring, tamp liberally in order to fill all cavities and prevent air pockets. If tamping does not eliminate all air pockets, drill small vent holes through the base surface.
5. Level off the grout flush with the top of the dam.
6. Allow the grout to cure at least 48 hours before tightening the foundation bolts or starting the pump.
Tighten pipe connections to suction and discharge flanges.
Check the pump alignment.
When the grout has thoroughly dried, paint the exposed edges to prevent air and moisture from coming in contact with the grout.
Installation Preparations
Inspection
All pump parts were carefully inspected before leaving the factory, but may have become soiled or damaged in shipping and handling or storage at site. The installer must therefore check that all parts are clean and undamaged before installing them.
Use appropriate solvent to wash off any protective coating from the shaft sections and wipe thoroughly clean and dry.
Dirt, sand, etc. in the system will cause premature wear on the critical pump internal surfaces, resulting in reduced pump performance.
Pumps and drivers mounted on a common base plate were accurately aligned before shipment. All base plates are flexible to some extent and, therefore, must not be relied upon to maintain the factory alignment.
Realignment is necessary after the complete unit has been leveled on the foundation and again after the grout has set and foundation bolts have been tightened. The alignment must be checked after the unit is piped and rechecked periodically as outlined in the following paragraphs. To facilitate accurate field alignment, we do not dowel the pumps or drivers on the base plates before shipment.
Engine Preparation
Safe and efficient operation of a pumping unit driven by an diesel engine, requires the installation to satisfy the following requirements:
- It is recommended that the operator become familiar with the installation and service manual supplied by the engine manufacturer or Peerless Pump
- Be well ventilated in order to keep the ambient temperature as low as possible. Taking 60 °F [15.6 °C] as a datum point, every 10 °F [-12 °C] rise in temperature reduces the horsepower of the engine by approximately 1 %.
- Provide ample air for proper combustion.
- Provide the engine with an efficient exhaust system so that the combustion gasses discharge with a minimum of backpressure.
- Provide for a fuel system of adequate capacity that meets the local codes.
- Provide ample accessibility to service engine.
- Provide correct rotation of the pump. Engine rotation is determined at the factory. No change of engine rotation can be made in the field.
Base Plate or Pump
Never attempt to lift the pump by means of eyebolts screwed into the driver mounting holes because the bolts are not strong enough to carry the weight of the entire pump.
Leveling
Flat surfaces that might capture air during grouting should be vented to prevent voids between the surface and the grout. The base plate should be leveled by use of wedges or by use of leveling screws supported on rectangular metal blocks.
The leveling screw threads should be covered with a non-binding material such as grease, putty or tape before grouting, to facilitate their removal.
If shims are used, they should be placed to isolate from the initial application of grout. After the initial grout has cured, the forms and shims may be removed and the void filled with a second application of grout.
A gap of about 0.75 to 1.5" [19.05 mm to 38.1 mm] should be allowed between the base plate and the foundation for grouting.
Grouting
The grout material that supports the base plate is a critical element of the pump support structure and should be carefully selected. The product warranty is void if this Instruction is not followed.
If the grout cracks or fails, the structure will be compromised. When the alignment is correct, the foundation bolts should be tightened evenly but not too firmly. The unit can then be grouted to the foundation. It is not recommended to grout leveling pieces, shims or wedges in place because they introduce discontinuities and stress concentrations that may cause the grout to crack. Foundation bolts should not be fully tightened until the grout is hardened, usually about 48 to 72 hours after pouring. Jacking screws should be removed after the grout has hardened and the holes filled with an appropriate sealing material.
Doweling
Contact Peerless Pump for more information.
Piping and Connections
Pipe Supports, Anchors or Joints
Suction and discharge piping should be anchored, supported and restrained near the pump to avoid application of forces and moments to the pump in excess of those permitted by Peerless Pump.
In order to achieve optimum operation and minimum noise and vibration, consider vibration dampening of the pump.
Noise and vibration are generated by the revolutions of the motor and pump and by the flow in pipes and fittings. The effect on the environment is subjective and depends on correct installation and the state of the remaining system.
Elimination of noise and vibrations is best achieved by means of a concrete foundation, vibration dampers and expansion joints.
The pump should also be inspected internally for foreign matter that may have entered the pump.
Vibration Dampers
To prevent the transmission of vibrations to buildings, isolate the pump foundation from building parts by means of vibration dampers.
The selection of the right vibration damper requires the following data:
- Forces transmitted through the damper
- Motor speed considering speed control, if any
- Required dampening in %.
The selection of vibration damper differs from installation to installation. In certain cases, a wrong damper may increase the vibration level. Vibration dampers should therefore be sized by the supplier of the vibration dampers.
If you install the pump on a foundation with vibration dampers, always fit expansion joints on the pump flanges. This is important to prevent the pump from "hanging" in the flanges.
Suction Piping
The suction and discharge piping should be of sufficient size and be internally free of foreign material.
Considerations for suction piping to achieve optimal performance are:
- When operating under suction lift, line must be kept absolutely free from air leaks.
- When operating under suction lift, must be at least one pipe diameter larger than the pump suction nozzle. In order to prevent eddies and vortices, the end of the suction pipe must be at least two pipe diameters below the free liquid surface. If a foot valve is used to facilitate priming, the foot valve must have a minimum flow area 1.5 times the area of the suction pipe. The suction at all points and should not contain loops or high spots in which air can be trapped.
- When operating under suction pressure, pipe may be equal to, but never less than the suction nozzle size.
Failure of the suction piping to deliver the liquid to the pump in this condition can lead to noisy operation, swirling of liquid around the suspended pump assembly, premature bearing failure and cavitation damage to the impeller and inlet portions of the casing.
Contact Peerless Pump for further information.
Suction Valves & Manifolds
Block valves may be installed to isolate the pump for maintenance.
Foot valves are specially designed non-return valves sometimes used at the inlet to prevent backspin caused by rapidly draining water in the discharge pipe.
Discharge Valves
A non-return valve and an isolation valve should be installed in the discharge pipe. The non-return valve serves to protect the pump from backflow and excessive backpressure. The isolation valve is used when starting and stopping the pump.
We recommend closing the isolation valve before stopping or starting the pump.
Pump backspin and hydraulic shock can cause severe damage to pump and motor. Install at least one non-return valve in the discharge pipe, not more than 25 ft. [7.5 m] after the discharge flange to help prevent this.
Operating some pumps at shutoff may cause a dangerous increase in pressure or power. If increasers are used on the discharge side of the pump to increase the size of piping, they should be placed between the non-return valve and the pump.
If expansion joints are used, they should be placed between the pipe anchor and the non-return valve.
Nozzle Loads
The piping should be aligned with the pump nozzles to minimize pump nozzle loads. Contact Peerless Pump for allowable nozzle loading for your given design.
Setting the Impeller Clearance
To achieve optimal performance and reduce radial loading, the impeller should be centered in the volute passageway of the casing. For new pumps, this is done at the factory.
Alignment
Pumps and drivers mounted on a common base plate were accurately aligned before shipment. All base plates are flexible to some extent and, therefore, must not be relied upon to maintain the factory alignment.
After the grout has set and the foundation bolts have been properly tightened, the unit alignment should be checked.
After the piping of the unit has been connected, the alignment should be checked again. Alignment may be checked by mounting a dial indicator to measure shaft movement before and after tightening flange bolts. If the unit does not stay in alignment after being properly installed, the following are possible causes:
- Setting, seasoning or springing of the foundation
- Excessive pipe strain distorting or shifting the machine
- Settling of the building
- Shifting of pump or driver on the base plate or foundation
To facilitate accurate field alignment, we do not dowel the pumps or drivers on the base plates before shipment.
Reliable, trouble-free, and efficient operation of a pumping unit requires correct alignment of pump and driver shafts.
Misalignment may be the cause of:
- Noisy pump operation
- Vibration
- Premature bearing failure
- Excessive coupling wear
Recheck alignment is required after:
Mounting
- Grout has hardened
- Foundation bolts are tightened or readjusted
- Piping is connected or adjusted
- Pump, driver or base plate is moved for any reason
The procedure for alignment verification for units with the pump and driver connected by a flexible coupling, mounted on a common base are:
- Disconnect the coupling halves.
- Set the coupling gap appropriately.
- Test for parallel and angular alignment with a straight edge and feeler gauge as shown in manufacturer's instructions (at the end of this section). With coupling halves stationary, make trials at four places 90 ° apart. Perfect alignment occurs when a straight edge is level across the coupling halves and the same gauge just enters between the halves, both conditions at all points.
- An alternate test for parallel and angular alignment may be made with a dial indicator mounted as shown in fig. 8.
- Scribe the index lines on the coupling halves (as shown) or mark where the indicator point rests.
- Set indicator dial to zero.
- Slowly turn BOTH coupling halves so that index lines match, or indicator point is always on the mark.
- Observe dial reading to determine whether pump or driver needs adjustment.
- Acceptable parallel and angular alignment occurs when total indicator reading (complete turn) does not exceed limits shown on either a tag or decal on the unit or on the unit outline drawing.
- When significant operating temperature differential will exist between the pump and driver (i.e. steam turbine drive with pump handling cold liquid), thermal growth will cause the hotter unit to rise. Compensate for this growth by initially setting the hotter unit 0.003" to 0.005" [0.076 mm to 0.127 mm] low. When both units are at normal operating temperature, a final check of coupling alignment must be made. Correct the alignment if necessary.
- NOTE Check for correct electric motor rotation as described in the two bullet points under paragraph 6.3 below while coupling halves are disconnected.
- Correct for excessive parallel and angular misalignment by slightly shifting the leveling wedges under the base plate. Tap lightly (in or out) with a hammer. Retest alignment after each shifting of a wedge.
- In some instances, for factory-aligned pumping units, it may be necessary to change the shims under the pump or driver, or even relocate these factory-positioned units on the base plate. Make such changes only after it is certain alignment cannot be obtained by shifting of the wedges.
- If wedges are shifted or shims changed a substantial amount to obtain proper alignment, recheck the piping alignment and level of the shafts.
Auxiliary (Driver, Coupling, etc.)
Engine Drivers
Engine driven unit are typically supplied with pump and drive on a common base plate. For units that are supplied separate, contact Peerless Pump.
- Check the axial misalignment between pump and engine.
- Check parallel alignment.
- Check the angle between the pump shaft and driver when coupled has a Maximum angle of 3 degrees. Consult manufacturer.
- At least 3/4 of the key is engaged with the coupler and the shaft.
- Installation of universal drive see manufacturer's instructions.
Lubrication, Priming and Cooling Systems
If supplied, please see additional documents attached to the pump or contact Peerless Pump.
Electrical Installation
Electrical conduit and boxes should be located to avoid obstruction of pump unit.
A plot of speed versus torque requirements during the starting phase of a pump can be checked against the speed versus torque curve of the driving motor. Contact the drive manufacture for curve availability. The driver should be capable of supplying more torque at each speed than required by the pump in order to accelerate the pump up to rated speed. This condition is generally easily attainable with standard induction or synchronous motors, but under certain conditions, such as highspecific-speed pumps over 5000 US units [100 metric units] or reduced voltage starting, a motor with high pull-in torque may be required. To achieve a smooth start for the pumping equipment, autotransformers may be connected to the starting panel or solid state starters used. These provide a gradual increase in voltage up to rated voltage, ensuring even acceleration.
Control, Monitoring & Alarm Equipment
All control and alarm systems should be checked for correct installation and functioning in accordance with the manufacturer's instructions. All alarm point settings should be checked.
Stopping the Unit/ Reverse Runaway Speed
A sudden power and/or discharge valve failure during pump operation against a static head will result in a flow reversal, and the pump will operate as a hydraulic turbine in a direction opposite to that of normal pump operation.
If the driver offers little resistance while running backwards, the rotational speed may approach the pump-specific speed.
This condition is called runaway speed and causes mechanical problems. Contact Peerless Pump for aid in preventing this condition.